The dU/dt at motor terminals normally is very different from the dU/dt that you can calculate from IGBT and its driving characteristics (turn on time, gate resistor, etc) at converter terminals. As the cable acts like a distributed LC impedance, the dU/dt calculation on inverter terminals will give you very high values that can be apparently dangerous, but in practice, will not happen at motor terminals.

For long cables, the combination of cable impedance, high frequency input impedance of motor and inverter switching frequency can lead to reflection of voltage pulses that gives origin to large voltage overshoots on motor terminals. The problem increases as increasing switching frequency because the time between voltage pulses will be smaller, so, a voltage pulse reaching the motor will add to the pulse being reflected. This “double pulsing” can results in extreme voltage overshoot and dU/dt that will result in motor insulation failures. For the inverter side the increasing switching frequency will be a problem (besides power losses) if you have a big capacitor filter at converter output, that can lead to high current pulses at inverter side.

The determination of the resulting dU/dt at motor terminals from the dU/dt at inverter terminals is very difficult if you try to use simulations. For this task you’ll need the high frequency parameters of cables (that also depends on installation details) and motor, that will not be available from standard datasheets and are very difficult to obtain from measurements. In practice almost all inverter manufacturers make extensive measurements and establish some criteria in order to orient applications. The approach is to determine if it is necessary or not to have an output filter for a known application (cable length).

For instance, a common specification is:

For cable lengths up to 100 meters (and motor suitable for inverter applications) it is not necessary a filter; for lengths from 100 to 200 meters, a series reactance can be used; for greater lengths it is necessary an LC filter at inverter terminals. The limit lengths can be different from different manufacturers and voltage levels (LV/MV). Gozuk, for instance, can give complete orientation for application of its drives considering the needed cable length for the application.

You may also like:

We know that the phase sequence is one of many conditions of the synchronization operation, and made in the beginning of construction. But if for any reason we need to check the phase sequence for two ...
Storage battery is an important component of UPS system. Choosing battery is not only related to the cost of the manufacturers, but also affecting the reliability of continuous power supply of UPS power. ...
AC drives are designed to provide variable speed control. They maintain the optimal speed required for an application to enhance production and save energy. Low- and medium-voltage drives gradually accelerate ...
AC Drives has to be selected by current and not power. That should be same but is not always. Immerged pumps for examples are using more current than standard ac motor for same mechanical power. In general ...
Noise and sound are a bit tricky to deal with. Generally the noise from the motor fan is "white noise" and not objectionable to the ear, except for large machines that were mentioned or as mentioned below. The ...
service The engineers in AC Drive China are very professional in Chinese automation industrial control fields, provide you comprehensive energy saving solutions.

Hot Tags

Featured

Frequency directly represents no of rotation of rotor for that machine, the higher the frequency the more the rotation of the rotor, i.e. the rpm of the motor there by result ... Due to power electronics technology and microelectronics technology rapid development, variable frequency drive reforms and upgrades speed also is faster, introduce new products, ... Since the 21st century, China variable frequency drive industry is highly fission. Many foreign brands begin to set up factories in China, the implementation of the localization ... My personal preference is for an AC line reactor simply because it does a better job of protecting the variable frequency drive from the line and the line from the drive. I've ... As nowadays there is a trend in green energy production and energy efficiency, what solutions/applications would you recommend in reduction consumed energy of a motor driven by ...

What's New