Off-Line testing using Motor Circuit Analysis
Motor Circuit Analysis (MCA) is a de-energized test method and the test can be initiated from the Motor Control Center (MCC) or directly at the motor. The advantage to testing from the MCC is the entire motor system, including the connections and cables between the test point and the motor, is evaluated.
ALL-TEST PRO MCA instruments apply a low voltage, non-destructive AC signal through the motor windings and measure the response to these signals. Winding faults are indicated by variances in the response to the applied signal through the windings. These variances cause unbalances in the measured response to the applied signal. Therefore, when testing 3-phase equipment such as motors, generators, or transformers the response of each phase is compared to the other two. When testing single phase devices or DC motors then the winding is compared to itself or compared to a like single phase device or a like DC motor.
ALL-TEST PRO MCA test instruments measure the phase angle (Fi), the current/frequency response (I/F), the impedance (Z) and depending upon the instrument, the resistance (R) and the inductance (L) of each winding. The unbalances of these measurements are compared and simple rules are used to determine the condition of the device under test. Moreover, each instrument will perform an insulation to ground test.
Computer software can be used to analyze the condition of the device under test and provide the user with a written report. Results can also be trended for identifying long term motor faults. I.e. used for Condition Based Maintenance or Predictive Maintenance purposes.
Additional investigation and analysis techniques are available to more thoroughly identify any of these variances in the winding so faults can be quickly and easily identified. These faults can be corrected or removed prior to energizing the winding preventing potential total destruction of the motor or other winding system.
For evaluation of the windings, whether a fault is developing between turns in a single coil, coils in the same phase, or coils across phases, the unbalance(s) between phases for the phase angle (Fi) and current/frequency response (I/F) measurements are evaluated.
The insulation to ground test is used to evaluate for conductor to ground issues.
Phase resistance is evaluated looking for connection issues, inductance is evaluated for possible rotor problems, and impedance and inductance matching are used to detect contamination or over-heating of the windings.
The off-line test takes only a few minutes and if testing from the MCC, the connections, cables and the motor are evaluated.
ALL-TEST PRO MCA instruments apply a low voltage, non-destructive AC signal through the motor windings and measure the response to these signals. Winding faults are indicated by variances in the response to the applied signal through the windings. These variances cause unbalances in the measured response to the applied signal. Therefore, when testing 3-phase equipment such as motors, generators, or transformers the response of each phase is compared to the other two. When testing single phase devices or DC motors then the winding is compared to itself or compared to a like single phase device or a like DC motor.
ALL-TEST PRO MCA test instruments measure the phase angle (Fi), the current/frequency response (I/F), the impedance (Z) and depending upon the instrument, the resistance (R) and the inductance (L) of each winding. The unbalances of these measurements are compared and simple rules are used to determine the condition of the device under test. Moreover, each instrument will perform an insulation to ground test.
Computer software can be used to analyze the condition of the device under test and provide the user with a written report. Results can also be trended for identifying long term motor faults. I.e. used for Condition Based Maintenance or Predictive Maintenance purposes.
Additional investigation and analysis techniques are available to more thoroughly identify any of these variances in the winding so faults can be quickly and easily identified. These faults can be corrected or removed prior to energizing the winding preventing potential total destruction of the motor or other winding system.
For evaluation of the windings, whether a fault is developing between turns in a single coil, coils in the same phase, or coils across phases, the unbalance(s) between phases for the phase angle (Fi) and current/frequency response (I/F) measurements are evaluated.
The insulation to ground test is used to evaluate for conductor to ground issues.
Phase resistance is evaluated looking for connection issues, inductance is evaluated for possible rotor problems, and impedance and inductance matching are used to detect contamination or over-heating of the windings.
The off-line test takes only a few minutes and if testing from the MCC, the connections, cables and the motor are evaluated.
Power factor is actually the factor of generated power utilized in performing useful work.
Ideally it is equal to 1, but practically it is always less than 1 as current always take time to reach at lower ...
A few years ago I wrote an article listing the things that can often fail in power supplies. Despite its simplicity, the article was the most downloaded on the website for a long time. Maybe that tells us ...
Due to power electronics technology and microelectronics technology rapid development, variable frequency drive reforms and upgrades speed also is faster, introduce new products, improve performance ...
Efficiency is built into a motor on design and on the quality of the steel that makes up the laminated core. The fan and bearings are also a factor. "T" frame motors have quite a heavy slot fill so there is ...
No matter what level of voltage you are dealing with, the ground wall insulation will be heavier than the conductor insulation. Potential to the ground wall is line voltage. Turn to turn voltage, especially in ...
The engineers in AC Drive China are very professional in Chinese automation industrial control fields, provide you comprehensive energy saving solutions.
Frequency directly represents no of rotation of rotor for that machine,
the higher the frequency the more the rotation of the rotor, i.e. the
rpm of the motor there by result ...
Due to power electronics technology and microelectronics technology rapid development, variable frequency drive reforms and upgrades speed also is faster, introduce new products, ...
Since the 21st century, China variable frequency drive industry is highly fission. Many foreign brands begin to set up factories in China, the implementation of the localization ...
My personal preference is for an AC line reactor simply because it does a better job of protecting the variable frequency drive from the line and the line from the drive. I've ...
As nowadays there is a trend in green energy production and energy efficiency, what solutions/applications would you recommend in reduction consumed energy of a motor driven by ...
What are the effects for a 50Hz motor running on 60Hz?
Variable Frequency Drive versus Soft Starter in Harmonics
Considerations in choosing large Variable Frequency Drive
Common Mode Noise Impact in AC drive Applications
AC drives in pumps for energy saving
HMI and SCADA system
Something need to be considered in buying AC drives
ABB sine wave filter
Variable Frequency Drive versus Soft Starter in Harmonics
Considerations in choosing large Variable Frequency Drive
Common Mode Noise Impact in AC drive Applications
AC drives in pumps for energy saving
HMI and SCADA system
Something need to be considered in buying AC drives
ABB sine wave filter