Blog Reading
Home » Blog » Energy saving » Transformer VS output filter in VFD and motor connection

Transformer VS output filter in VFD and motor connection

You might want to use an isolation transformer between the variable frequency drive and the motor if the VFD is long distance from the motor.
But you should caution in applying an isolation transformer between the output of a drive and a motor. Most standard transformers are not designed to have a PWM voltage applied to the primary. Also, the transformer impedance is going to be in the 5% to 7% range which could introduce enough voltage drop that the motor would not be able to achieve its rated output HP.

Applying an isolation transformer or line reactor typically adds impedance, but adds little real motor protection.
An output filter typically adds a resistive/capacitive circuit that mitigates the harmful "spikes", protecting both the motor and wiring especially as the distance between the motor and VFD drive increases.

There are transformers available that are designed to work with the variable frequency / variable voltage of an inverter, but they can be pricey. The right filter can protect most motor windings, even at long lead lengths. In either configuration there will be additional losses and care needs to be taken to ensure adequate voltage at the motor terminals.
Much of the shaft performance and related efficiency of an induction motor is dependent on the rotor bar slot configuration and slot material (such as the aluminum or copper mentioned earlier). These slot designs provide better shaft performance and reduced heating on inverter waveform resulting in better efficiency overall.
A note of caution here is the consideration of across the line ('ATL') starting of an inverter-optimized rotor design. This type of rotor behaves more like a NEMA design ‘A’ with higher inrush during high-slip (‘ATL’ starting) situations. Often a higher overload protection setting is required, and the motor may struggle to start the connected load in some instances.

You may also like:

By controlling the discharge of working fluid into the turbine, you control the Torque produced by the turbine and thereby the Power output. The minimum discharge required to keep the system at the required ...
In DC breaking, frequency inverter injects DC current in stator of Motor & with that DC current Stator will try to lock the rotor. There will be stationary field instead of rotating field in between stator ...
I was recently trying to connect my Delta VFD E series drive with my laptop using Vfd-Soft software (which I downloaded from Delta website) and RJ 45 to USB converter(RS232/RS485 converter). I connected the ...
Before the proper spacing of ground rods can be determined, the site needs to be evaluated to determine the soil conductivity. Some of the software programs used for grounding system design resulted in ...
INVERTER-READY means that some of the extras required to protect the machine from the damaging effects of the drive output waveform are included. INVERTER-DUTY (also sometimes listed as "inverter ready") ...
service The engineers in AC Drive China are very professional in Chinese automation industrial control fields, provide you comprehensive energy saving solutions.

Hot Tags

Featured

Frequency directly represents no of rotation of rotor for that machine, the higher the frequency the more the rotation of the rotor, i.e. the rpm of the motor there by result ... Due to power electronics technology and microelectronics technology rapid development, variable frequency drive reforms and upgrades speed also is faster, introduce new products, ... Since the 21st century, China variable frequency drive industry is highly fission. Many foreign brands begin to set up factories in China, the implementation of the localization ... My personal preference is for an AC line reactor simply because it does a better job of protecting the variable frequency drive from the line and the line from the drive. I've ... As nowadays there is a trend in green energy production and energy efficiency, what solutions/applications would you recommend in reduction consumed energy of a motor driven by ...

What's New